14/2 12/2 150m 100m nmd90 for canada 300v 600v electrical wire domestic house building cable C-SA CUL Certificate
APPLICATIONS
NMD90 cables may be used for both exposed work in dry locations or concealed work in dry or damp locations.
The maximum allowable conductor temperature is 90°C.
The minimum recommended installation temperature is -25°C for two-conductor cables and -10°C for three-conductor cables (with suitable handling procedures).
Material should be properly stored above 0°C for 24 hours prior to installation.
The maximum voltage rating for all intended applications is 300 volts.
Consult the Canadian Electrical Code1 for further information related to applications.
CODES / STANDARDS
NMD90 cables meet or exceed the following requirements:
CONSTRUCTION
ASTM
C.S.A. C22.2 No. 48 (non-metallic sheathed cable)
Canadian Electrical Code1
NMD90 cables are available as two- or three-conductor cables with a bare grounding conductor.
It is manufactured using annealed (soft) copper conductors-compressed standing for stranded conductors;
a heat-resistant thermoplastic polyvinyl chloride (PVC) insulation and nylon jacket for the individual conductors with a PVC jacket for the overall construction.
Conductors are white, black and red (for 3 conductor cables). Cable jackets are colour coded by size for quick identification in the Table below
JACKET COLOUR CODE - Typical Application Guide
• WHITE - General Residential Wiring
• RED - 2 Black and Red conductors - 208V-240V Circuits (no neutral)
• ORANGE - No. 10 AWG General Residential Wiring
• YELLOW - No. 12 AWG General Residential Wiring
• BLUE - No. 14 AWG - 2 black and white conductors - 120V Arc Fault Circuit Interupter Applications
Specification | |||||||||||||
Conductor | Insulation | Ground | Approx. Jacket thickness | Approx. Cable Dia. | Approx. Cable weight | Allowable Ampacities 30°C | |||||||
Size | Cores | Strands | Inches | mm | Size | Core | Inches | mm | Inches | mm | Ib/ | Kg/ | |
(AWG) | (AWG) | 1000ft | km | ||||||||||
14 | 2 | 1 | 0.034 | 0.86 | 14 | 1 | 0.03 | 0.76 | 0.388*0.192 | 9.86*4.88 | 68 | 101 | 25* |
14 | 2 | 1 | 0.034 | 0.86 | 14 | 1 | 0.03 | 0.76 | 0.388 x 0.192 | 9.86 x 4.88 | 68 | 101 | 25* |
12 | 2 | 1 | 0.034 | 0.86 | 14 | 1 | 0.03 | 0.76 | 0.422 x 0.209 | 10.71 x 5.30 | 86 | 129 | 30* |
10 | 2 | 1 | 0.034 | 0.86 | 12 | 1 | 0.03 | 0.76 | 0.481 x 0.230 | 12.21 x 5.84 | 122 | 182 | 40* |
8 | 2 | 7 | 0.04 | 1.02 | 10 | 1 | 0.045 | 1.14 | 0.636 x 0.312 | 16.15 x 7.92 | 208 | 310 | 55 |
6 | 2 | 7 | 0.051 | 1.3 | 8 | 7 | 0.045 | 1.14 | 0.792 x 0.370 | 20.12 x 9.40 | 315 | 468 | 75 |
14 | 3 | 1 | 0.034 | 0.86 | 14 | 1 | 0.03 | 0.76 | 0.345 | 8.77 | 86 | 128 | 25* |
12 | 3 | 1 | 0.034 | 0.86 | 14 | 1 | 0.03 | 0.76 | 0.381 | 9.69 | 114 | 169 | 30* |
10 | 3 | 1 | 0.034 | 0.86 | 12 | 1 | 0.03 | 0.76 | 0.427 | 10.85 | 163 | 242 | 40* |
8 | 3 | 7 | 0.04 | 1.02 | 10 | 1 | 0.045 | 1.14 | 0.57 | 14.47 | 275 | 408 | 55 |
6 | 3 | 7 | 0.051 | 1.3 | 8 | 7 | 0.045 | 1.14 | 0.695 | 17.65 | 421 | 627 | 75 |
3 | 3 | 7 | 0.051 | 1.3 | 6 | 7 | 0.08 | 2.03 | 0.925 | 23.48 | 799 | 1189 | 115 |